Compact, economical general-purpose inverter for small automation equipment — controls and regulates 3-phase induction (IM) motor speed; V/f and sensorless vector (SVC) control.

S600/S600E is a mini-type open-loop vector inverter — the upgrade of the previous generation, with more specific functions. The considerate operation methods offer great convenience to the user.
| Callout | Part |
|---|---|
| LED display area | LED display area |
| Current running parameter unit indication | Current running parameter unit indication |
| Program key | Program key |
| Enter key / Shift right key | Enter key / Shift right key |
| Motor capacity and input power | Motor capacity and input power |
| AVI/ACI mode dip switch | AVI/ACI mode dip switch |
| NPN/PNP mode dip switch | NPN/PNP mode dip switch |
| Panel potentiometer | Panel potentiometer |
| Up/Down key | Up/Down key |
| Stop/Reset key | Stop/Reset key |
| Running key | Running key |
| RS485 network interface | RS485 network interface |
| External terminals | External terminals |
| Item | Explanation | |
|---|---|---|
| Control characteristic | Control mode | V/f control, open loop vector control |
| Range of output frequency | 0 ~ 500.00 Hz | |
| Frequency setting resolution | 0.01 Hz | |
| Output frequency resolution | 0.01 Hz | |
| PWM carrier frequency | Adjustable from 0.5 kHz to 12 kHz | |
| Torque boost | 1 Hz / 150 % | |
| V/f curve | Three types: line, multi-point, Nth power V/f curve(1.2th, 1.4th, 1.6th, 1.8th, 2th power) | |
| V/f separation | Two types: full separation, semi-separation | |
| Jump frequency | Adjustable from 0.1 Hz to 500.00 Hz | |
| Acceleration / deceleration time | 0.00 to 65000 seconds (4-stage acceleration/deceleration time set independently)Linear or S-curve acceleration/deceleration mode | |
| Over current stall prevention level | Set according to the motor load characteristics, within 100 ~ 200 % of the rated current of the drive | |
| DC brake | When stopping, operates from 0.00 Hz to the maximum operating frequency; braking current 0 ~ 100 % of the rated currentStart time 0 ~ 100.0 seconds, stop time 0 ~ 100.0 seconds | |
| Brake torque | 20 % (an external optional brake resistor reaches 125 %) | |
| Speed ratio | Open loop vector control: 1 : 100 | |
| Operation characteristic | Frequency setting — keypad | Set by the ▲ / ▼ keys |
| Frequency setting — external terminal | DC 0–10 V, DC 4 ~ 20 mA, serial communication (RS485) | |
| Operation signal — keypad | Operated by the RUN and STOP keys | |
| Operation signal — external terminal | 2-wire / 3-wire operation, jog operation, serial communication (RS485) | |
| Input terminal of multi-function | Forward and reverse running, three-wire operation control, forward and reverse jog running, free stop, reset fault, running pause, external fault input, increment/decrement frequency terminal setting, 16-segment preset speed switching, acceleration/deceleration time switching, frequency source switching, running command switching, PID control, PLC status reset, prohibit acceleration and deceleration, length count, high-speed pulse frequency, stop DC braking, clear the running time. | |
| Output terminal of multi-function | Inverter operation, fault output, frequency level detection FDT output, frequency arrival, zero speed operation, overload pre-alarm, count value arrival, length arrival, PLC cycle completion, cumulative running time arrival, frequency limitation, torque limit, ready to run, upper limit frequency arrival, lower limit frequency arrival, undervoltage status output, communication setting, cumulative power-on time arrival, frequency arrival output, timing arrival output, offload, reverse in operation, zero current state, module temperature reached, output current exceeds the limit, lower limit frequency arrival (also when stopped), alarm output (keeps running), running time arrival. | |
| Analog signal output | Corresponds to the actual output frequency, output current, output voltage, etc. | |
| Fault signal contact | Contact "ON" (relay or two open collector outputs when the AC drive fails) | |
| Inner function | Output frequency upper and lower limit setting, instantaneous power failure restart, abnormal fault restart, speed tracking, simple PLC, multi-speed operation, PID control, timing control, automatically regulated output, abnormal record, parameter lock, parameter factory reset, reverse rotation prohibited, over current stall prevention, over voltage stall prevention, electronic thermal relay. | |
| Protection function | Short circuit protection, acceleration over current, deceleration over current, constant speed over current, acceleration over voltage, deceleration over voltage, constant speed over voltage, bus undervoltage fault, motor overload, inverter overload, over torque protection, loss phase on the output, module overheating, external fault, communication fault, current detection fault, parameter read and write abnormality, inverter hardware abnormality, motor short circuit to ground, running time arrival, power-on time arrival, the load dropped, the PID feedback disconnected, fast current limit timeout. | |
| Keypad | Contains a 5-digit 8-segment LED display and 7 status indicator LEDs; sets the frequency, displays the actual output frequency, output current and a user-defined unit; parameter browsing and modification, parameter locking, abnormal fault display; run, stop, reset, forward/reverse, jogging. | |
| Environment | Operation temperature | −10 ℃ ~ +40 ℃ |
| Temperature of stock | −20 ℃ ~ +60 ℃ | |
| Humidity of operation environment | Below 90 % RH, no condensation | |
| Height of installation | No more than 1000 m in height, no corrosive gas, liquid or dust | |
| Vibration | < 20 Hz: 9.80665 m/s² (1G) · 20 ~ 50 Hz: 5.88 m/s² (0.6G) | |
| Enclosure | IP20 (depending on the end customer's installation environment) | |
220 V single phase / three phase series
| Item | Specification | |||||
|---|---|---|---|---|---|---|
| S600/E-2T***G | 0.4 | 0.75 | 1.5 | 2.2 | 4.0 | |
| Output | Max. motor output power(kW) | 0.4 | 0.75 | 1.5 | 2.2 | 4.0 |
| Max. motor output power(HP) | 0.5 | 1 | 2 | 3 | 5.4 | |
| Output rated capacity(kVA) | 1.1 | 1.5 | 2.7 | 3.7 | 6.5 | |
| Output rated current(A) | 2.3 | 4.0 | 7.0 | 9.6 | 17.0 | |
| Output frequency range | 0 ~ 500 Hz | |||||
| Overload capacity | 150 % — 60 s | |||||
| Max output voltage | Same as input voltage | |||||
| Input | Phase, voltage, frequency | Single phase / three phase 200 ~ 240 V 50/60 Hz | ||||
| Voltage & frequency variations | Voltage ±15 %, frequency ±5 % | |||||
| Input current — single phase(A) | 5.4 | 8.2 | 14.2 | 23 | ✕ | |
| Input current — three phase(A) | 3.1 | 5.0 | 7.7 | 11.1 | 22.2 | |
| Cooling method | Fan cooling | |||||
Three phase 440 V series
| Item | Specification | |||||
|---|---|---|---|---|---|---|
| S600/E-4T***G | 0.75 | 1.5 | 2.2 | 4.0 | 5.5 | |
| Output | Max. motor output power(kW) | 0.75 | 1.5 | 2.2 | 4.0 | 5.5 |
| Max. motor output power(HP) | 1 | 2 | 3 | 5.4 | 7.4 | |
| Output rated capacity(kVA) | 1.9 | 2.9 | 3.9 | 6.9 | 9.9 | |
| Output rated current(A) | 2.5 | 3.8 | 5.1 | 9 | 13 | |
| Output frequency range | 0 ~ 500 Hz | |||||
| Overload capacity | 150 % — 60 s | |||||
| Max output voltage | Same as input voltage | |||||
| Input | Phase, voltage, frequency | Three phase 380 ~ 460 V 50/60 Hz | ||||
| Voltage & frequency variations | Voltage ±15 %, frequency ±5 % | |||||
| Input current(A) | 3.4 | 5.0 | 5.8 | 10.5 | 15 | |
| Cooling method | Fan cooling | |||||
Inverter size
| Type | W | W1 | W2 | H | H1 | D | M | Fig. |
|---|---|---|---|---|---|---|---|---|
| S600/E-2T0.4G | 68 | 56 | — | 141 | 120 | 132.2 | 5 | Size 1 |
| S600/E-2T0.75G | 68 | 56 | — | 141 | 120 | 132.2 | 5 | Size 1 |
| S600/E-4T0.75G | 68 | 56 | — | 141 | 120 | 132.2 | 5 | Size 1 |
| S600/E-4T1.5G | 68 | 56 | — | 141 | 120 | 132.2 | 5 | Size 1 |
| S600/E-2T1.5G | 135.5 | 124.5 | 124.5 | 146.5 | 135.5 | 130.9 | 5.3 | Size 2 |
| S600/E-2T2.2G | 135.5 | 124.5 | 124.5 | 146.5 | 135.5 | 130.9 | 5.3 | Size 2 |
| S600/E-2T4.0G | 135.5 | 124.5 | 124.5 | 146.5 | 135.5 | 130.9 | 5.3 | Size 2 |
| S600/E-4T2.2G | 135.5 | 124.5 | 124.5 | 146.5 | 135.5 | 130.9 | 5.3 | Size 2 |
| S600/E-4T4.0G | 135.5 | 124.5 | 124.5 | 146.5 | 135.5 | 130.9 | 5.3 | Size 2 |
| S600/E-4T5.5G | 135.5 | 124.5 | 124.5 | 146.5 | 135.5 | 130.9 | 5.3 | Size 2 |
| S600/E-4T2.2G | 78 | 66 | — | 132 | 122 | 135.7 | 5.2 | Size 3 |
Parameter function description
| Parameter | Parameter function | Setting range | Setup parameter |
|---|---|---|---|
| 00-02 | Main frequency source selection | 0 ~ 5 · 6: communication setting (remote keypad) · 7 ~ 9 | 6 |
| 00-11 | Parameter initialization | 0 ~ 2 · 3: copy inverter parameters to keypad · 4: copy keypad parameters to inverter | 3 or 4 |
Remote keypad failure code description
| Failure code | Description | Possible reason | Corrective measures |
|---|---|---|---|
| CErr | Communication error | Communication interrupted twice | 1. Check whether a broken line occurs, or whether the peripheral equipment has a strong interference source. 2. Return to the factory. |
| EErr | I2C communication error | I2C communication error with the MCU | Return to the factory. |
| uErr | Inverter type no match | Inverter type does not match | Use the correct inverter type. |
| dErr | Data invalid | Data invalid | Copy the inverter parameters to the keypad first. |
| nErr | Operation error | Operation error | Return to the factory. |
Parameter function description
| Parameter | Parameter function | Setting range | Setup parameter |
|---|---|---|---|
| 00-02 | Main frequency source selection | 0 ~ 5 · 6: communication setting (remote keypad) · 7 ~ 9 | 6 |
| 00-11 | Parameter initialization | 0 ~ 2 · 3: copy inverter parameters to keypad · 4: copy keypad parameters to inverter | 3 or 4 |
Remote keypad failure code description
| Failure code | Description | Possible reason | Corrective measures |
|---|---|---|---|
| CErr | Communication error | Communication interrupted twice | 1. Check whether a broken line occurs, or whether the peripheral equipment has a strong interference source. 2. Return to the factory. |
| EErr | I2C communication error | I2C communication error with the MCU | Return to the factory. |
| uErr | Inverter type no match | Inverter type does not match | Use the correct inverter type. |
| dErr | Data invalid | Data invalid | Copy the inverter parameters to the keypad first. |
| nErr | Operation error | Operation error | Return to the factory. |
Remarks:
Send us the load, voltage and application — QS engineering helps pick the model code, cable and matching accessories.